AESZP0BA – AC1 SSL SENSORED - FREE VERSION - User Manual Page - 67/73
the Driver of the Elecromechanical Brake is short circuited)
and this alarm occurs.
b) When the feedforward PWM is higher than 70% of the
battery voltage, the Actual voltage on the
Electromechanical Brake is expected high. If it is lower than
14V it means the Electromechanical Brake always gets the
truck Braked (probably the Driver of the Elecromechanical
Brake is opened) and this alarm occurs.
- Remedy: Probably it is necessary to substituite the controller because the
driver of the Electromechanical Brake has a failure.
5) MDI VALVE2 SHORT
MDI-PRC Code = 70
- Cause: This alarm occurs on the MDI-PRC and the information is
transferred via CAN Bus to the AC1.
- Remedy: See 14.2 and the manual of the MDI-PRC.
6) MDI NEVP1 NOT OK
MDI-PRC Code = 90
- Cause: This alarm occurs on the MDI-PRC and the information is
transferred via CAN Bus to the AC1.
- Remedy: See 14.2 and the manual of the MDI-PRC.
7) MDI PEV NOT OK
MDI-PRC Code = 89
- Cause: This alarm occurs on the MDI-PRC and the information is
transferred via CAN Bus to the AC1.
- Remedy: See 14.2 and the manual of the MDI-PRC.
8) MDI DRV 2 OPEN
MDI-PRC Code = 75
- Cause: This alarm occurs on the MDI-PRC and the information is
transferred via CAN Bus to the AC1.
- Remedy: See 14.2 and the manual of the MDI-PRC.
9) MDI DRV 2 SHORT
MDI-PRC Code = 74
- Cause: This alarm occurs on the MDI-PRC and the information is
transferred via CAN Bus to the AC1.
- Remedy: See 14.2 and the manual of the MDI-PRC.
10) INPUT ERROR #1
MDI-PRC Code = 92
- Cause: This alarm occurs when the PLD device has a failure. The PLD
device is used for both, the Passive Emergency Cell (see 5.1)
and a Multiplexer on the Main Lifting/Lowering requests. This
Multiplexer exits the Lifting and the Not Lifting level on two
distinct addresses. When the Lifting and the Not Lifting outputs
have the same Logic Level the PLD device has failed and this
alarm occurs.
- Remedy: It is necessary to substituite the controller.
11) ANALOG INPUT
MDI-PRC Code = 96
- Cause: This alarm occurs when the A/D conversion of the analog inputs
gives frozen value, on all of the converted signals, for more