AESZP0BA – AC1 SSL SENSORED - FREE VERSION - User Manual Page - 15/73
7.4 Main contactor and key connection
- The connection of the main contactor can be carried out following the
drawing in Figure 7–1.
- An intrinsic protection is present inside the logic when the voltage on the
battery power connection overtakes the battery nominal voltage more than a
certain percentage. Thank to this protection, it is allowed that the Main
Contactor (or an emergency switch) breaks the Battery positive in every
moment regardless of the state of the key (without this protection, if the Main
Contactor breaks when a regenerative braking is in progress, the rail
capacitor voltage increases and the overvoltage could damage the Power
Mosfets).
Figure 7–1